There are some opportunities that come along for homeowners that seem too good to be true, and most of your parents and grandparents can tell you if it looks this way it probably is. But, how about quick return on your investment that will continue to save money for the life of your boiler? This is what an outdoor reset control will do for them. Add the feature of a more comfortable home and most people start asking: What is the catch? The catch is the technician needs to not only sell this product, but install it correctly and educate the customer on the new use of the boiler.
When installing an after-market outdoor reset control on a non-condensing boiler, be sure to keep the minimum Return Water temperature above 115F. Most recommendations state 120F to avoid condensing on the sections and in the flue. The installation of said control will save an estimated 15% of the annual fuel costs! The same percentage in AFUE as the difference between an EnergyStar boiler versus conventional.
Next, make sure you educate the homeowner on how to operate the new boiler control. This more energy efficient option provides the minimum amount of heat to match the load based on outdoor temperature. Common sense can tell us we don't need 100% of the capacity unless we are at, or below the outdoor design temperature. In MA this design temperature is likely around 0F. The boiler temperature is generally set for 180F, this is the maximum the boiler operates at to meet the heat loss on a design day. But, when it is warmer outdoors you don't need 180F water anymore, and you can be more comfortable by turning that temperature down. Unfortunately, this makes your programmable thermostat almost obsolete. You see, a large set back with a thermostat (more than a couple degrees) will take hours, even a full day, to recover if using an outdoor reset controller. I see this a lot when homeowners replace a boiler with a rebate eligible option and never get the education needed on the operation.
I have heard arguments regarding increased electrical consumption since your circulator will now run for almost infinite periods of time. Luckily, our Manufacturer friends have thought of this and developed some amazing pumps over the last couple of years. Most of these ECM pumps will operate at minimum 50% less than their counterpart PSC pump. To put it into friendly terms, instead of approximately 84 watts, these new pumps can range from 9-42 watts, depending on load. As more zones turn on, the pump will need to speed up to maintain the gallons per minute (GPM) or temperature differential settings.
That all being said, I would recommend installing both of these: an outdoor reset control and ECM pump on any boiler without one! It is not a code requirement, but it probably should be.
Have a Domestic Hot Water Indirect? They have a priority setting for that.
Can't run the sensor wire outdoors in the mechanical room? There are wireless versions that are now cheaper than the traditional controls!
Don't live in fear of your customers saying no - and put the inventory on your trucks! It will amaze you how fast they move...
Example Boiler Heating Curve